Features - AC/DC Power Supplies
-
Fully Encapsulated
Chassis Mountable
Current Limit Short Circuit Protection
Low Output Ripple and Noise
Excellent Line and Load Regulation Characteristics
Free-Air Convention Cooling: No external Heat Sink
Required
High Current Output Models
- 5 V @ 5 amp; model 955
- 5 V @ 5 amp; model PWR-01
Wide Input
Voltage Range
- 105 Vac to 125 Vac: Model 955
- 85 Vac to 205 Vac: Model PWR-01
|

Models:
Order
Now PWR-01 |
|
Overview
Analog Devices' line of compact AC/DC modular supplies
offer system designers a means of supplying a reliable, easy to use,
low cost solution to powering the 5B Series and 6B Series Signal
Conditioning subsystems. These models provide high accuracy, short
circuit protected, regulated outputs with very low noise and ripple
characteristics. All models contain threaded inserts to facilitate
ease of mounting on the rear of the AC1363 19" rack
mount kit. Screw terminals also provide ease of connections to both
AC line supply and backplane power input terminals. |
|
Model Descriptions
Three models are offered in power levels of 5 watt
(Model 955) and 25 watt (Model PWR-01). High power, 25 watt, versions
are supplied with plus and minus line sense terminals to facilitate
remote load regulation. Two AC input voltage ranges provide the capability
of handling varying line supply applications: 120 Vac (Model 955)
and 120/240 Vac (Model PWR-01). These AC/DC supplies combine the
advantages of both switching and linear regulated supplies in a small
compact package. Using the switching regulator technique provides
Model PWR-01 with high efficiency characteristics. The linear regulation
method of Model 955 offers low levels of output noise and ripple
- 2 mV rms, max. Model 955 provides a fixed 5 Vdc output (±2%
max. accuracy), while Model PWR-01 offers an adjustable 5 Vdc output
(±1% accuracy with ±3% adjustment range) and a "Power
On" LED light. |
|
| Fusing
If AC supply input fusing is desired, use a slow
blow type fuse that is rated for 150% to 200% of the power supply's
full load AC input. As a rule of thumb, the full load AC input current
is typically 28 mA for each 1 watt of output power. Model PWR-01
is provided with an internal, nonreplaceable, 2 ampere slow blow
fuse on the AC supply line. To protect signal conditioning modules,
should internal faults occur, all supplies are designed to clamp
at an output voltage of 6.2 volts. |
|
|
Mechanical Outline Drawings
Refer to the Outline
Drawings section for mechanical drawings on Models 955 and
PWR-01. |
|
|
Determining Power Requirements
The total 5B system power requirement is a function
of the modules and backplanes that are selected. Individual requirements
are listed in the following tables:
5B
Series Module Current Requirements
|
5B
Series Backplanes
and Mounting
Card Current Requirements
| 5B01 |
0 mA |
| 5B02 |
32 mA |
| 5B03 |
0 mA |
| 5B04 |
0 mA |
| 5B08 |
0 mA |
| 5B08-MUX |
40 mA |
| AC1360 |
0 mA |
|
|
|
5B Series
Power Supply Specifications
(typical @ +25°C and nominal line voltage)
| Input Voltage Range |
105 V rms to 125 V rms |
85 V rms to 265 V rms |
| Frequency |
50 Hz to 250 Hz |
47 Hz to 63 Hz |
| Internal Line Fuse |
N/A |
250 Vrms, 2 A Slo Blow |
| Output Voltage |
5 Vdc |
5 Vdc1 |
| Remote Sense Terminals |
N/A |
Yes |
| Short Circuit Protection2 |
Current Limited |
Current Limited |
| Overvoltage Protection |
+6.2 V dc |
+6.0 V dc |
| Output Current |
1000 mA |
5000 mA |
| Voltage Accuracy |
±2% maximum |
±1%1 |
| Temperature Coefficient |
±0.02%/°C |
±0.05%/°C |
| Line Regulation |
±0.05% |
±0.1% |
| Load Regulation |
±0.15% |
±0.5% |
| Ripple & Noise |
2 mV pk-pk maximum |
50 mV pk-pk maximum |
| Breakdown Voltage |
2500 V rms, minimum |
2500 V rms, minimum |
| Switching Frequency |
N/A |
65 kHz |
| Operating Temperature Range |
-25°C to +71°C |
0°C to +70°C |
| Storage Temperature Range |
-25°C to +85°C |
-40°C to +85°C |
| Cooling |
Free Air Convection |
Free Air Convection |
| Chassis Mount; Encapsulated |
Yes |
Yes |
| Mounting Threaded Inserts |
Four, 4-40 x 0.15" |
Four, 4-40 x 0.15" |
|
1Adjustable ±3%
2Substantial overload can be withstood, including
direct short. Prolonged operation should be avoided since excessive
temperature rises will occur.
Specifications subject to change without notice. |
|
|
| |
|